Self-contained, hydraulically controlled, oil-insulated single-phase reclosers with a series trip coil; Types 6H and V6H are the three-phase versions of the H group. Also sold as Kyle 4H recloser, Kyle Type L recloser, McGraw-Edison Kyle recloser, Eaton Cooper Power series single-phase recloser, Kyle 6H recloser. New surplus, used, or failed. Send the nameplate, get a written offer.

Get an offer

What it is

The nameplate is on the head casting under the sleet hood and shows the type, serial number and coil rating. Photograph the nameplate, the operations counter, and the yellow operating and non-reclosing handles. Note whether the bushings are standard or extra-creepage.

TypeSelf-contained, hydraulically controlled, oil-insulated single-phase reclosers with a series trip coil; Types 6H and V6H are the three-phase versions of the H group
ManufacturerCooper Power Systems, Kyle 4H recloser, Kyle Type L recloser, McGraw-Edison Kyle recloser, Eaton Cooper Power series single-phase recloser, Kyle 6H recloser
On the nameplateH, 4H, V4H, L, V4L, E, 4E, V4E, D, DV, 6H, V6H
2.4 to 14.4 kV typesH (50 A, 1,250 A interrupting), 4H (100 A), V4H (200 A), L (280 A), V4L (280 A, 6,000 A interrupting)
24.9 kV typesE (100 A, 2,500 A interrupting), 4E (280 A, 4,000 A), V4E (280 A, 6,000 A)
560 A typesD (2.4 to 14.4 kV) and DV (24.9 to 34.5 kV), oil interrupting
Three-phase H group6H (100 A) and V6H (200 A): phases trip individually, all three lock out together
BIL95 kV (H), 110 kV (4H, V4H, L, V4L, D), 150 kV (E, 4E, V4E, DV)
Interrupting mediumOil in E, 4E, H, 4H, L and 6H; vacuum in V4H, V4L, V4E and V6H
Rating basisSeries trip coil size; minimum trip is twice the coil rating (140% on X coils)
Read the catalog number

How to read a Cooper Kyle hydraulic recloser catalog number.

Catalog 280-10 builds E, H and L group catalog numbers in order: basic letters (KH for H group, KE for E group, KL for L group), a type digit (omitted for E and L, 1 for H, 4 for 4H or 4E, V4 for V4H, V4E or V4L, 6 for 6H, V6 for V6H), the series coil rating in amps, the delayed time-current curve letter (A if all operations are fast), then the number of fast operations and the number of delayed operations (four total at most). The worked example below is printed in the catalog; the others are built from the same published scheme.

KH4100B22
Type 4H, 100 A series coil, B delayed curve, 2 fast and 2 delayed operations

Not sure? Type it into the catalog lookup or text a photo of the label.

What drives the number
  • Vacuum-interrupting versions (V4H, V4L, V4E, V6H) need less maintenance than oil-interrupting types.
  • Larger coil ratings and the 24.9 kV E group are less common than small H-group units.
  • Oil condition and counter reading tell a buyer how hard the unit has worked.
  • Failed and untested units are bought for metal content.
  • Units built before 1980 may contain PCBs; we sample before an offer is final.
  • We do not publish prices. Metal, demand, and condition move them. You get a written number for your unit.
From the yard

The letter V placed before the type (V4H, V4L, V4E, V6H) means vacuum interrupters. Every unit's rating comes from its series trip coil, so two 4H reclosers can have very different minimum trips. A hookstick lever under the sleet hood sets the non-reclosing feature for one operation to lockout during hot-line work. Eaton now lists the E, 4E, H, 4H and L types as discontinued, so remaining units are surplus and used stock. H and L group units (110 kV BIL and below) are not suited to single-phase taps of 14.4/24.9 kV systems. E group units are rated 24.9 kV and can serve single-phase taps of 20/34.5 kV systems where 150 kV BIL is adequate.

Photos we need

Three photos price most Cooper Kyle hydraulic recloser offers.

01

The label

The catalog number, straight on and in focus. For a pallet, one label per model plus a count.

02

The unit

Front, sides, and anything damaged. Doors open if it has them.

03

The lot

The whole pallet or shelf. New in box: the box labels.

The nameplate is on the recloser head or tank. Photograph it with the type, voltage, continuous current, and interrupting rating in frame. Photograph the control nameplate and the control face separately.

How selling works
  1. 01
    Send the nameplate

    Photos or a list with counts. Text, email, or the form.

  2. 02
    We read it and reply

    During business hours, by whatever contact method you picked.

  3. 03
    You get a written offer

    Per unit or per lot. A range if we need to sample or test, firm after. Freight is in the number.

  4. 04
    We pick up and pay

    Our truck and our rigging. Wire or ACH within 3 business days of a passed inspection.

Freight: Single-phase hydraulic reclosers are light enough for a liftgate truck. Three-phase units and their frames need a forklift or crane. We plan it.

FAQ

Selling a Cooper Kyle hydraulic recloser: what people ask.

Yes. We buy H, 4H, L, E and 4E reclosers of any age and condition. Units built before 1980 may contain PCBs; we sample before an offer is final.

Selling a Cooper Kyle hydraulic recloser? Send the nameplate.